Description
-
BrandYokogawa
-
ModelPW484-50 S1
-
Product NameDCS Power Supply Module
-
Place of OriginJapan
-
HS Code8537.10.90
-
Dimensions49.7 mm × 130 mm × 146.5 mm
-
Weight1.0 kg
-
Operating Temperature−20 °C to +70 °C
-
Storage Temperature−40 °C to +85 °C
-
Power Supply24 V DC
-
Warranty1year
-
Product Statusnew and original
Yokogawa PW484-50 S1
Voltage:
Input supply voltage:
24VDC ±10% DC input;
provides regulated 5VDC backplane bus voltage for FIO rack I/O modules;
built-in over-voltage protection function;
isolation voltage between input power and internal circuit.
Current:
Max input current:
5.5A@24VDC;
output current for FIO backplane 5VDC bus;
integrated over-current, short-circuit and thermal protection;
supports 1+1 redundant parallel current sharing for non-stop power supply.

Yokogawa PW484-50 S1 Troubleshooting: Unstable Voltage and Current
Fluctuating external 24VDC input results in unstable 5VDC backplane voltage and current output from PW484-50 S1
Root cause: Fluctuation of external 24VDC power source; loose input power terminals; reversed input power polarity; excessive ripple on input power supply.
Action: Measure external 24VDC power source and ensure it stays within 24VDC ±10% tolerance; retighten input power terminals; validate correct positive-negative polarity; install DC power filter when ripple exceeds technical specifications.
Total FIO rack load exceeds the rated output capability of PW484-50 S1
Root cause: Excessive quantity of I/O modules powered by a single PW484-50 S1; total backplane load current surpasses module rated value.
Action: Calculate overall load current of the FIO rack; decrease I/O module quantity for this power unit; implement 1+1 redundant parallel configuration for PW484-50 S1 to realize load-current sharing.
Abnormal current-sharing performance under 1+1 redundant parallel mode
Root cause: Unbalanced current distribution between two PW484-50 S1 modules; poor contact on redundant bus connector; mismatched hardware revisions of power modules.
Action: Inspect redundant parallel bus connector condition; make sure both power modules adopt identical hardware revision; re-insert both power modules firmly; monitor output-current balance of each individual module.
Intermittent voltage and current jitter caused by module over-temperature protection
Root cause: Insufficient cabinet ventilation; ambient operating temperature out of allowable range; heat sink clogged with accumulated dust.
Action: Remove dust from module surface and heat sink; enhance cabinet cooling and air convection; maintain operating ambient temperature within -20℃ ~ +70℃.
Backplane bus short-circuit or abnormal partial load brings about output-current swing
Root cause: Short-circuit fault on FIO rack backplane; faulty I/O module dragging down backplane bus voltage; short-circuit failure on rear terminal blocks.
Action: Power down the rack and remove all I/O modules; energize PW484-50 S1 under no-load status and verify whether 5VDC output returns stable; plug in I/O modules sequentially to identify defective I/O unit; check rack backplane for foreign-caused short-circuit points.
Hardware performance degradation of PW484-50 S1 power module
Root cause: Aging of internal electronic components; historical damage from over-voltage or over-current events; internal circuit failure.
Action: Conduct hot-swap operation with verified good spare PW484-50 S1; compare voltage-current output performance; replace the faulty module if the symptom vanishes after replacement.