Description
-
BrandWoodward
-
Model8200-1300
-
Product Name505D Digital Steam Turbine Controller
-
Country of OriginUSA
-
HS Code8538900000
-
Dimensions430mm*320mm*150mm (16.9in*12.6in*5.9in)
-
Weight4.5 kg (9.9 lb)
-
Operating Temperature‑30 °C to +70 °C
-
Storage Temperature‑40 °C to +85 °C
-
Humidity5%–95% RH
-
Warranty12 month
-
Product StatusNew and original
Woodward 8200-1300 Product Overview and Technical Specifications
Input/Output:
Analog Inputs: 8 configurable (4-20 mA / 1-5 Vdc)
Discrete Inputs: 20 contact inputs
Analog Outputs: 2 × 4-20 mA (control signals)
Relay Outputs: 8 (for alarms, trips, and auxiliary devices)
Communication: 1 × RS-232/RS-485 (Modbus RTU), 2 × Ethernet TCP/IP ports
Expansion: Supports LINKnet I/O modules (up to 16 analog inputs, 4 analog outputs, 16 discrete inputs/outputs)
Key Features:
Five PID Controllers: Speed/load, extraction/admission, cascade, Aux-1, Aux-2
Triple-Redundant 32-bit Processors: Ensures ±0.25% speed regulation accuracy
Multiple Startup Modes: Manual, semi-automatic, automatic, remote
Integrated Protection: Overspeed, critical speed avoidance, max power, overpressure, and more
8.4-inch Color Display: 34-key keypad (including emergency stop) for local operation
SOE Recorder: Captures 512 events with 1 ms resolution
Product Advantages:
1.Precision Control: Advanced algorithms optimize efficiency and reduce thermal stress
2.Safety & Reliability: SIL 3-certified TMR architecture prevents unsafe operation
3.Flexible Connectivity: Dual Ethernet and Modbus enable integration with DCS, PLC, and SCADA
4.Easy Configuration: User-friendly software for PID tuning, logic programming, and diagnostics
5.Harsh Environment Ready: Wide temperature range and NEMA 4X rating suit industrial sites
Applications:
1.Power Generation: Combined-cycle plants, cogeneration systems, 10-100MW steam turbines
2.Oil & Gas: Turboexpanders, compressor drives, pipeline pressure control
3.Process Industries: Chemical, petrochemical, and pharmaceutical plant steam systems
4.District Heating: Steam turbine‑based CHP (combined heat and power) plants
5.Core Functions:- Speed/Load Regulation: Maintains precise turbine speed or generator load
6.Startup/Shutdown Control: Executes configurable sequences for safe operation
7.Protection & Tripping: Triggers alarms/trips for overspeed, overpressure, and faults
8.Data Logging & Diagnostics: Real‑time monitoring, SOE recording, and predictive maintenance data
9.System Integration: Exchanges data with plant-wide automation systems via standard protocols
Power Supply:
Operating Voltage: 18-32 VDC (LVDC, -15% to +20%)
Current Consumption: 4.3 A max
Power Consumption: <140 W
Enclosure Rating: NEMA 4X / IP66
Certifications: SIL 3 (IEC 61508), ATEX Cat 3, Class I Div 2 (A/B/C/D)