Description
-
BrandWoodward
-
Model8237-2600
-
Product NameProTech-GII Panel-Mount Overspeed Protection System
-
Country of OriginUSA
-
HS Code8538900000
-
Dimensions483mm*356mm*159mm
-
Weight11.3 kg (25 lb)
-
Operating Temperature‑20 °C to +65 °C
-
Storage Temperature‑40 °C to +85 °C
-
Humidity5%–95% RH
-
Warranty12 month
-
Product StatusNew and original
Woodward 8237-2600 Product Overview and Technical Specifications
Input:
Speed Sensors: 3 × MPU (Magnetic Pickup) inputs, 0.5-32,000 rpm range
Discrete Inputs: 6 × external trip inputs (vibration, pressure, etc.)
Analog Input: 1 × 4-20 mA for speed readout
Output:
Trip Relays: 3 × independent or 2-out‑of-3 voted relays (5 A @ 250 VAC)
Analog Output: 1 × 4-20 mA (speed retransmission)
Communication: Modbus TCP/IP and RS-485 for diagnostics and monitoring
Power Supply:- Dual Inputs: HV (90-264 VAC/100-150 VDC) and LV (18-32 VDC)
Consumption: 30 W max; 0.5 A @ 90 VAC, 0.22 A @ 264 VAC
Certifications: IEC 61508 SIL 3, CE, ATEX Zone 2
Product Advantages:
SIL 3 Safety: Certified for high-integrity protection in hazardous environments
Flexible Configuration: Selectable voted/independent relay outputs for diverse safety logic
Seamless Integration: Modbus connectivity for DCS/SCADA integration
Minimized Downtime: Hot-swap and diagnostic LEDs reduce maintenance time
Harsh Environment Durability: Withstands high vibration, humidity, and temperature fluctuations
Applications:
Power Generation: Steam/gas turbine overspeed protection in combined-cycle and cogeneration plants
Oil & Gas: Turboexpander and compressor drive safety systems
Process Industries: Chemical, petrochemical, and refinery turbine safety interlocks
Hydroelectric Plants: Hydro turbine overspeed and runaway prevention
Core Functions:
Overspeed/Overacceleration Detection: Monitors 3 MPU inputs for abnormal speed spikes
Safety Tripping: Activates relays to shut down turbines during critical faults
Diagnostic Monitoring: Real-time LED indicators and Modbus-based health monitoring
Event Logging: SOE records trip/alarm events for root-cause analysis
System Testing: Supports manual/automatic overspeed tests without process disruption
Key Features:
TMR Architecture: Three independent processing channels for fault tolerance
High-Speed Response: 12 ms trip time for overspeed/overacceleration events
Hot-Swap Modules: Online replacement of A/B/C modules without shutdown
SOE Recording: 512-event log with 1 ms resolution for trip analysis
Vibration & Shock Resistance: Compliant with IEC 721‑3‑3 Class 3C2