Description
-
BrandGE
-
ModelDS200TCEBG1BAA
-
Product NameProtective Termination Expander Board
-
Place of OriginUnited States
-
HS Code8537101190
-
Dimensions178mm × 159mm × 32mm
-
Weight0.75 kg
-
Operating Temperature-30°C ~ +65°C
-
Storage Temperature-40°C ~ +80°C
-
Power Supply24VDC
-
Warranty12 MONTH
-
Product StatusNEW BRAND
Backed by abundant in-stock inventory and nearly 20 years of industry experience, our company stands as a leading player in the industrial control sector.We offer an extensive range of industrial control products covering numerous models. Should you have any other requirements, please feel free to contact us, and we will respond to you promptly.
Our main brand:
1.ABB's module cards, touch screens, controllers, etc., such as PP846 touch screen, IGCT starting with 5SHY, PM starting controller, AI, DO starting input/output module, SP starting Bailey module, etc
2.GE's module card CPUs, such as VMIC starter, IS200, IS215, IS400, IS420 series, etc,
3.Emerson's card components and EPRO probes, Westinghouse 1C series, Honeywell CC series, Schneider 140 series, Envision full series, Bentley 3500 series, Rexroth motors and drives, and Foxboro small modules.
Inputs:
Field digital contact signals sourced from turbine protection circuits, covering trip interlock signals, fault status contacts and discrete emergency shutdown signals
Inter-board digital signals transmitted from core control boards through ribbon cable connectors (JKX, JKY, JKZ)
Backplane power supply input: +5 VDC power supplied by the Mark V rack backplane
Conditioned protection signals delivered from safety monitoring boards
Outputs:
Buffered discrete protection signals forwarded to neighboring Mark V control modules
Terminated relay driving outputs for on-site alarm devices and protection interlock equipment
Processed trip logic signals sent to overspeed modules and safety control boards
Signal distribution outputs used to expand terminal capacity for various protection loops
Interface Connectors:
3 × 20-pin connectors: JKX, JKY, JKZ
1 × 26-pin connector
4 × 10-pin connectors

Pre-Troubleshooting Notes
Carry out Lockout/Tagout (LOTO) protocols and disconnect cabinet power prior to board removal. Wear a grounded ESD wrist strap to avoid electrostatic damage to electronic components.
Fault 1: Lost discrete input signals or unstable signal readings
Inspect field contact wiring and terminal fastening status, and check for loose connections, open circuits or short circuits.
Examine JKX, JKY, JKZ ribbon cables for bent pins, improper engagement and corrosion. Reconnect or substitute faulty cables as needed.
Test onboard signal transformers to identify open windings or insulation breakdown.
Check for heavy electromagnetic interference from adjacent power cables and optimize shielding grounding arrangements.
Fault 2: Failed protection signal output and inactive interlock triggers
Measure the backplane +5 VDC supply voltage to verify stable power supply.
Inspect wiring of output channels connected to relays and alarm devices for short-circuit damage.
Cross-check jumper settings against engineering schematics and rectify incorrect configurations.
Monitor internal signal status via Mark V Toolbox to confirm if faults stem from upstream control boards.
Fault 3: Intermittent signal variations and sporadic false protection alarms
Remove oxidation and dust buildup on connectors, backplane contacts and terminal blocks.
Check cabinet ventilation conditions to resolve overheating that leads to component performance drift.
Route signal cables away from high-power cables to minimize noise interference.
Ensure all cable shielding implements single-point grounding.
Fault 4: Communication errors between the TCEB board and core control boards
Reinstall the board firmly in the rack slot to achieve reliable contact with the backplane.
Inspect all 20-pin, 26-pin and 10-pin connectors for bent or fractured pins.
Conduct module swapping with a spare DS200TCEBG1BAA to differentiate board faults from rack backplane defects.
Fault 5: No power indication on the board
Measure the +5 VDC power output of the target rack slot on the backplane.
Examine the PCB for burnt traces, damaged discrete components and other visible defects.
Check for conductive foreign matter triggering short circuits on the circuit board.
General Troubleshooting Guidelines
Document fault codes and signal status collected by Mark V Toolbox before executing maintenance work.
Never insert or extract the board while the cabinet is energized, which may result in unexpected turbine trips.
If comprehensive inspection excludes wiring and power supply failures, the board needs off-line maintenance or replacement.
Run complete loop tests on all protection circuits after troubleshooting to confirm proper functionality.

Frequently Asked Questions (FAQ)
1.How fast will you reply to my inquiry?
We process all inquiries efficiently and will respond promptly once we receive your message.
2.Do you carry large inventory of industrial control parts?
We maintain massive ready stock of mainstream automation spare parts to shorten lead times.
3.Can you source discontinued or obsolete PLC & DCS modules?
Absolutely.
We specialize in sourcing hard-to-find, obsolete and out-of-production industrial control components.
4.Do you inspect goods before shipment?
Every product undergoes thorough inspection before packing and dispatch.
5.Can you ship orders worldwide?
We provide global shipping with flexible logistics for urgent and regular orders.
6.What payment methods are available?
We accept multiple secure payment options. Please contact our sales team for detailed terms.