Description
-
BrandABB
-
ModelBC810K02
-
Product NameCEX-Bus Redundant Interconnection Unit Complete Kit
-
Place of OriginSweden
-
HS Code8538909999
-
DimensionsWidth 59mm, Height 185mm, Depth 127.5mm
-
Weight1.5kg
-
Operating Temperature0℃ ~ +60℃
-
Storage Temperature-40℃ ~ +70℃
-
Part Number3BSE031155R1
-
Warranty12 month
-
Product StatusNew and original
Backed by abundant in-stock inventory and nearly 20 years of industry experience, our company stands as a leading player in the industrial control sector.We offer an extensive range of industrial control products covering numerous models. Should you have any other requirements, please feel free to contact us, and we will respond to you promptly.
Our main brand:
1.ABB's module cards, touch screens, controllers, etc., such as PP846 touch screen, IGCT starting with 5SHY, PM starting controller, AI, DO starting input/output module, SP starting Bailey module, etc
2.GE's module card CPUs, such as VMIC starter, IS200, IS215, IS400, IS420 series, etc,
3.Emerson's card components and EPRO probes, Westinghouse 1C series, Honeywell CC series, Schneider 140 series, Envision full series, Bentley 3500 series, Rexroth motors and drives, and Foxboro small modules.
1. Power Supply Input
Rated input voltage: 24 VDC;
Allowable voltage range: 19.2 VDC ~ 30 VDC (±20% tolerance);
Typical operating current: 50 mA;
Maximum operating current: 70 mA;
Typical power dissipation: 1.2 W;
Built-in reverse polarity, overvoltage and short-circuit protection;
Protection class: IP20 (only for cabinet installation).
2. CEX-Bus Differential Communication I/O
Bus signal level: 5 V differential signal;
Static bus current per port: ≤12 mA;
Supported bus termination: 120 Ω matched resistor;
Transmission mode: full-duplex differential transmission, anti-interference design.
3. Backplane Bus I/O
Backplane working voltage: 5 VDC;
Maximum load current for single backplane port: 150 mA;
Signal type: single-ended digital logic signal.
4. External Auxiliary Interface
No analog input/output and relay contact output; only dedicated CEX bus interconnection ports.
5. LED Indicator Output
Passive indicator light drive: 3.3 V low-current LED, single indicator current ≤5 mA;
Indicators: Power, Run, Bus Fault, Link status.
6. Environmental Electrical Limits
Operating temperature: 0 ℃ ~ +55 ℃;
Storage temperature: -40 ℃ ~ +70 ℃;
Humidity: 5%~95% RH, non-condensing.

1. Preparation Work
Fully cut off the cabinet overall power supply to ensure complete power outage of the rack system; wear qualified anti-static wristband connected to cabinet grounding point to eliminate static electricity.
Visually inspect BC810K02 module, TP857 mounting baseplate, TK851 CEX-Bus dedicated cables and TB850 bus terminators, confirm no cracks, pin bending, oxidation, abrasion or deformation on all accessories. Prepare screwdriver and multimeter for subsequent inspection.
2. DIN Rail Baseplate Installation
Mount the TP857 baseplate onto standard TH35 top-hat DIN rail inside the control cabinet, push the baseplate horizontally until the buckle is fully clamped and fixed without sliding.
Connect the grounding terminal of the baseplate to cabinet equipotential grounding copper bar, guarantee stable and low-resistance equipment grounding. Reserve sufficient heat dissipation space around the baseplate, keep a clearance above 20mm between adjacent modules.
3. Module Installation and Locking
Align the golden finger connector on the back of BC810K02 with the socket on TP857 baseplate, insert the module horizontally and push steadily inward.
Press the module locking buckle on both sides until a clear click sound is heard, confirm the module is closely fitted and cannot shake or loose; avoid violent extrusion to prevent pin damage.
4. Wiring and CEX-Bus Connection
Connect 24VDC power lines to the dedicated power terminals of the baseplate strictly according to polarity definition, fasten terminal screws moderately to avoid loose wiring or thread slipping.
Use dedicated TK851 shielded cables for series connection between BC810K02 modules to build CEX-Bus link; keep signal cables separated from high-power power cables to reduce electromagnetic interference.
Install TB850 120Ω terminators at the two farthest endpoints of each independent bus segment; do not add extra terminators in the middle of the bus.
5. Pre-Power-On Comprehensive Inspection
Check all terminals, bus connectors and module buckles one by one to ensure tight fixation; use a multimeter to detect short-circuit risk between power positive and negative poles.
Detect the resistance of bus endpoints to confirm the terminator is normally 120Ω; double-check grounding continuity and cable wiring sequence to eliminate wrong wiring.
6. Power-On Commissioning and Verification
Restore cabinet 24VDC power supply slowly, observe the module indicator lights: keep PWR light always on steadily, RUN light constant on normally.
Observe bus fault indicator stays off, confirm no communication alarm; test upper system CEX-Bus online status, verify BC810K02 can normally interact data with SM810 controller, complete installation acceptance.

Frequently Asked Questions (FAQ)
1.How fast will you reply to my inquiry?
We process all inquiries efficiently and will respond promptly once we receive your message.
2.Do you carry large inventory of industrial control parts?
We maintain massive ready stock of mainstream automation spare parts to shorten lead times.
3.Can you source discontinued or obsolete PLC & DCS modules?
Absolutely.
We specialize in sourcing hard-to-find, obsolete and out-of-production industrial control components.
4.Do you inspect goods before shipment?
Every product undergoes thorough inspection before packing and dispatch.
5.Can you ship orders worldwide?
We provide global shipping with flexible logistics for urgent and regular orders.
6.What payment methods are available?
We accept multiple secure payment options. Please contact our sales team for detailed terms.