Description
-
BrandBently Nevada
-
Model3500/33-01-00
-
Product NameRelay Output Module
-
Dimensions349 mm × 206 mm × 30 mm
-
Weight0.82 kg
-
Place of OriginUnited States
-
HS Code8537101190
-
Operating Temperature-20 °C to +60 °C
-
Storage Temperature-40 °C to +85 °C
-
Power Supply0.28 A
-
Warranty12 month
-
Statusnew and original
Application Cases of Bently Nevada 3500/33-01-00 16-Channel Relay Module
Case 1: Large-Scale Refinery Centrifugal Compressor Unit (Oil & Gas Industry)
Mounted within the 3500 machinery protection rack, the 3500/33-01-00 receives Alert, Danger and Not-OK status over the backplane bus from vibration, thrust position and speed monitoring modules. Separate relay channels are assigned for high bearing vibration, excessive axial displacement and sensor-loop faults. Dry-contact relay outputs trigger local audible-visual alarms and transmit discrete alarm status to the DCS. The module delivers on-site annunciation and control-room remote notification for compressor-train auxiliary alarms, minimizing nuisance trips of main trip logic and enhancing overall system reliability.
Case 2: Steam Turbine Auxiliary Units in Thermal Power Plants (Power Generation Industry)
This module serves rotating auxiliary machinery for turbine-generator sets, such as condensate pumps, circulating-water pumps and boiler induced-draft fans. Multiple relay channels are mapped individually to vibration over-range, sensor faults and module diagnostic alarms. Latched-alarm mode is selected for unattended auxiliary equipment monitoring. Once an abnormality occurs, relay contacts hold the alarm state until manually reset by on-site operators. It provides distinct fault indication for auxiliaries without engaging main-unit emergency-trip logic, consolidating multi-signal outputs in one module to save cabinet installation space.
Case 3: Reciprocating Compressor in Petrochemical Ethylene Complex
Working alongside vibration and temperature monitoring modules, the unit processes multi-point alarm events including cylinder vibration, bearing temperature and crankcase operating conditions. Each relay channel is assigned to one independent alarm event. Dry-contact signals are fed to the safety instrumented system and local alarm panel, enabling operators to quickly identify faulty measurement points from relay status. It provides pre-danger-threshold early-warning alerts, facilitates predictive maintenance scheduling and helps prevent unplanned outages induced by sudden mechanical failures.
Case 4: Blast-Furnace Blower System for Metallurgical Works
Integrated into the 3500 machinery-protection rack for blowers, the module outputs discrete alarm signals for casing vibration, bearing temperature and sensor-circuit failures to the PLC interlock system and field alarm lamps. Non-latching configuration applies to general warning alarms, while latched mode is enabled for significant auxiliary danger alerts. Early-warning signals are isolated from critical trip-protection logic, allowing clear differentiation between minor fault hints and equipment-trip conditions and reducing nuisance-trip hazards for vital blast-furnace assets.
Case 5: Remote Unattended Pumping Station
Applied for condition monitoring of multiple transfer pumps. The 3500/33-01-00 aggregates alarm status from each pump’s vibration-monitoring channels and drives relay outputs for local indicator lamps and discrete-input points of the remote SCADA system. Latched relay settings preserve alarm records even after transient signals return to normal. On-site staff must complete inspection and manual reset prior to equipment restart, supporting secure operational management for unmanned pumping-station facilities.

Commissioning Procedure for Bently Nevada 3500/33-01-00 16-Channel Relay Module
1. Pre-commissioning Preparation
Verify stable 24 VDC backplane power supply for the 3500 rack and normal operation of the rack interface module.
Confirm firmware compatibility; 3500 Rack Configuration Software Version 3.3 or higher is required.
Prepare digital multimeter, wiring drawings, project backup files and work permits, and implement LOTO lock-out-tag-out safety procedures.
Ensure associated monitoring modules for vibration, thrust position, rotational speed and other parameters are physically installed and pre-configured within the rack project file.
2. Hardware Installation & Wiring Inspection
Insert the 3500/33-01-00 module into an available slot 2-14 of the 3500 rack and push firmly to achieve reliable backplane connection.
Terminate relay dry-contact terminals including COM, NO and NC to field devices such as local alarm panels and discrete input points of DCS or PLC systems.
Ensure all terminal screws are adequately tightened. Route relay signal cables separately from high-power cables to mitigate electromagnetic interference.
Confirm relay contact loads remain within rated specifications. Fit intermediate relays for heavy-load applications.
Power up the rack. A steady-green OK LED on the module indicates normal startup; a red LED signifies hardware faults.
3. Module Self-test
Connect a PC running configuration software to the 3500 rack and establish stable communication.
Navigate to Utilities → System Events / Module Self-test, select the slot assigned to 3500/33-01-00 and initiate a complete module self-test, which takes approximately 30 seconds to finish.
Refresh the system event log and confirm the self-test result shows PASS. Perform fault diagnosis if any failure events are logged.

4. Software Configuration
Open the target rack project and add the 3500/33-01-00 module under its corresponding slot location.
Access the Relay Association configuration page, select required relay channel pairs and tick the “Active” checkbox to enable relevant channels.
Define alarm trigger logic: select alarm sources including Alert, Danger and Not-OK from corresponding monitoring channels, and configure ANDor OR-logic operations according to site process requirements.
Configure critical parameters for each relay channel:
Latching or non-latching operating mode
Energize-on-alarm or de-energize-on-alarm for fail-safe logic design
Activate bypass or inhibit functions via software switches if relay outputs need temporary suppression during commissioning.
Save the project file and download the full configuration to the 3500 rack.
Perform an upload from the rack to cross-check download integrity and parameter consistency.
5. Dry-contact Output Simulation Test
Disconnect field load circuits or isolate interlock logic prior to testing.
Method 1: Force alarm status for target monitoring channels within configuration software.
Method 2: Inject simulated sensor signals to trigger Alert, Danger or Not-OK alarms on relevant monitoring modules.
Measure continuity across relay COM-NO and COM-NC terminals with a multimeter:
Validate contact switching actions upon alarm activation.
Verify contact reset behaviour after alarm conditions disappear for non-latching channels.
Confirm maintained contact state for latching relays and test manual reset functions through rack-interface push-buttons or software commands.
Test every configured relay channel sequentially and document all test results.
6. End-to-end System Verification
Re-establish field wiring connections for relay outputs.
Re-apply simulated alarm conditions.
Confirm correct status feedback from local audible-visual alarms and status changes at DCS or PLC discrete-input points.
Ensure no unintended interlock or alarm actions occur.
Remove simulated alarm conditions and verify signal restoration matches configured logic rules.
7. Post-commissioning Confirmation
Clear all simulated alarms and return the whole system to normal operating status.
Inspect the system event log to eliminate persistent module faults or communication errors.
Save the final complete rack-configuration file for official archiving.
Re-enable interlock protection logic strictly following work-permit procedures.
Complete the commissioning report and record firmware versions, channel allocation tables and logic descriptions.
8. Common Troubleshooting Items during Commissioning
Relay fails to operate: Check channel enable status, selected alarm trigger sources, successful configuration download and module OK-health status.
Contact logic operates inversely to expectations: Review energize-on-alarm / de-energize-on-alarm software settings. The 3500/33 module contains no physical jumpers for NO/NC contact reversal.
Latching relay cannot be reset: Validate assigned reset sources including local push-buttons, software commands or remote dry contacts.
Sporadic unintended relay switching: Inspect wiring tightness, cable shielding quality and physical separation from high-voltage power cables.

3500/22-01-01-01
3500/22 288055-01
1900/65A
24765-02-01
3500/91-01-01-01
3500/44-02-01
TK-3E
177313-02-01
1900/65A-01-01-04-CN-00
2300/20-CN