Description
-
BrandBently Nevada
-
Model3500/92-04-01-00
-
Product NameCommunication Gateway Module
-
Place of OriginUnited States
-
Customs HS Code85423190
-
Power Supply10 Mbps
-
Dimensions241 mm × 24.4 mm × 242 mm
-
Weight0.82 kg
-
Operating Temperature30 °C to +65 °C
-
Storage Temperature‑40 °C to +85 °C
-
Warranty12 month
-
Product Statusnew and original
3500/92-04-01-00 Bently Nevada Communication Gateway
Input:
Power input: 24 VDC nominal operating voltage; operating current 0.35 A typical, maximum 0.5 A, supplied from 3500 rack backplane.
Internal rack bus input: Receives monitoring data, alarm status and diagnostic information from other 3500 series modules within the rack.
Serial interface input: RS-232, RS-422, RS-485 for Modbus RTU slave, SNP slave communications; signal logic level 5 V differential.
Ethernet input: RJ45 10BASE-T Ethernet port for Modbus/TCP, Bently Nevada proprietary protocol, accepts connection from configuration software and host system.
Output:
Serial interface output: RS-232/RS-422/RS-485 transmits rack measurement values, alarm status to external automation devices (PLC, DCS) via Modbus RTU; 5 V differential signal output, limited drive current for communication signals only, no power-supply output.
Ethernet output: RJ45 10BASE-T outputs Modbus/TCP data and proprietary protocol data to host computer, configuration tool and upper-level control system.

3500/92-04-01-00 Bently Nevada Communication Gateway Wiring
Power Wiring
No external field power connections are needed. The module receives nominal 24 VDC power from the 3500 rack backplane, with a typical operating current of 0.35 A and a maximum current of 0.5 A. Once the module is seated into a full-height rack slot, the internal rack bus connection is completed automatically. Hot-swap operation is supported.
RS-232 Wiring (DB-9 male front-panel connector)
This interface is intended for local setup and troubleshooting, implementing point-to-point direct connection to a notebook PC or configuration terminal.
Shielded serial cable shall be applied, with a maximum transmission distance of 15 meters.
It adopts 5 V logic signal level; no power output is available from RS-232 pin assignments.
RS-422 / RS-485 Wiring (terminal block / DB-9 connector, Modbus RTU slave mode)
Wire differential signal pair A(+) and B(-) to the serial communication port of external PLC or DCS equipment.
Shielded twisted-pair cable is required; the maximum bus cable length for RS-485 is 1200 meters.
The cable shield should be earthed at one single point on the host-system side; shield grounding at the module side is prohibited.
Fit 120 Ω terminating resistors at both physical extremities of the bus for long-run wiring scenarios.
Galvanic isolation is provided between serial communication ports and rack internal circuits.
Ethernet Wiring (RJ45 10BASE-T)
Adopt star network topology. Connect this port to network switches, host computers or DCS networks for Modbus/TCP and Bently Nevada proprietary protocol communication.
Shielded CAT5 twisted-pair Ethernet cable is recommended.
Maximum allowable cable length is 100 meters.