Description
-
BrandGE
-
Model489‑P5‑LO‑A20‑E
-
Product NameGenerator Management Relay
-
Place of OriginCanada
-
Customs HS Code85362000
-
Power Supply20‑60 VDC
-
Dimensions229 mm × 254 mm × 254 mm
-
Weight8.6 kg
-
Operating Temperature‑20 °C to +60 °C
-
Storage Temperature‑40 °C to +85 °C
-
Warranty1year
-
Product Statusnew and original
GE 489-P5-LO-A20-E
Inputs
Analog Current Inputs: 5 A phase CT secondary inputs
Analog Voltage Inputs: Phase VT secondary up to 200 V AC, neutral VT 100 V AC
RTD Inputs: Up to 12 RTD inputs (100 Ω Pt, 100 Ω Ni, 120 Ω Ni, 10 Ω Cu) for temperature monitoring
Digital Inputs: 8 opto-isolated digital inputs, 24 V DC sinking type with 6 mA nominal operating current
Power Supply Input: 20-60 V DC or 20-48 V AC (48-62 Hz), for LO low-power variant
Outputs
Relay Outputs: 8 Form-C relay contacts, rated 5 A @ 250 V AC and 0.5 A @ 30 V DC, configurable for trip, alarm and control applications
Analog Outputs (A20 option): 4 programmable 4-20 mA analog outputs with ±1% full-scale accuracy, assignable to current, voltage, power, frequency and temperature signals
Communication Ports: Front-panel RS232 port, two isolated RS-485 ports, 10 Mbps 10Base-T Ethernet (RJ45)
Supported Communication Protocols
Modbus RTU, Modbus TCP/IP, DNP 3.0
Compatible Software
GE Vernova EnerVista 489 Setup Software: Supports device configuration, metering data viewing, COMTRADE oscillography analysis, and sequence-of-events log review.
Interoperable with third-party SCADA and DCS systems via the above-mentioned communication protocols.
Compatible Operating Systems & Host Systems
PC host: Windows XP, Windows 7, Windows 10 (32-bit / 64-bit) for running EnerVista software.
Field integration: Generic DCS / SCADA platforms supporting Modbus RTU, Modbus TCP/IP or DNP 3.0; compatible with GE Multilin SR-series protection devices.

Commissioning Procedure for GE 489-P5-LO-A20-E
Safety Notes:
All high-voltage wiring must be completed with power removed.
Use a secondary injection test set to verify relay functions.
Do NOT apply primary high voltage to the relay during commissioning.
1. Pre-Power Inspection
Verify mechanical mounting, ventilation, and cabinet grounding.
Confirm wiring per schematic:
Power supply: LO model 20-60 VDC / 20-48 VAC, polarity and insulation.
CT secondary: shorted before power-on; ratio and polarity verified.
VT secondary: voltage range correct; no short circuit.
RTD wiring: 2-wire / 3-wire / 4-wire connections.
Digital inputs (24 VDC sinking) and relay outputs (trip/alarm).
4-20 mA analog outputs (A20 option) and communications: RS232, isolated RS-485, Ethernet RJ45.
Ensure all terminals are tight; no shorts or loose connections.
2. Power Up & Self-Test
Apply auxiliary power only; keep CT/VT primary de-energized.
Observe front panel LEDs; confirm successful self-diagnosis with no hardware faults.
Record firmware version and model identification.
3. Connect to EnerVista 489 Setup Software
Connect PC via front RS232, rear RS-485 (with F485 converter), or 10Base-T Ethernet.
Open EnerVista 489 Setup, add device, and configure communication settings: baud rate, address, IP.
Establish online connection, read existing setpoints, and save the original configuration as backup.
4. Basic System Configuration
Set parameters per motor/generator nameplate and project requirements:
System: CT primary/secondary, VT ratio, nominal frequency.
RTD channels: type (Pt100, Ni100, Ni120, Cu10) and assigned functions.
Digital inputs: mapping to breaker status, remote trip, external alarms, etc.
Relay outputs: assign 8 Form-C contacts to trip, alarm, and control logic.
Analog outputs (A20): assign 4-20 mA sources (current, voltage, power, temperature) and full-scale ranges.
Communications: Modbus RTU/TCP, DNP3.0 addressing, baud rate, IP, subnet, gateway.
Protection settings: thermal overload, overcurrent, over/undervoltage, loss of field, negative sequence, earth fault, start-up protection. Enter thermal model: FLC, cold/hot ratio, allowed starts.
Logic: interlocks, breaker control, alarm schemes.
Write settings to the relay, verify values, and save the commissioning file.
5. Static I/O Testing (Secondary Injection Recommended)
Digital Inputs: Activate each input; confirm status updates on the HMI and software.
Relay Outputs: Use software force commands (safe offline mode) to operate each output; verify contact action and indication.
Analog Inputs: Inject simulated CT/VT signals; compare measured values. Simulate RTD resistance; validate temperature accuracy.
Analog Outputs (A20): Verify 4-20 mA outputs with a multimeter; confirm ±1% FS accuracy.
Protection Elements: Inject test signals to trigger each function; verify pickup, operating time, trip/alarm outputs, LEDs, event logs, and COMTRADE records.
6. Communication Testing
Test Modbus RTU/TCP: read measurements, statuses, and events; confirm stability and data integrity.
Test DNP3.0 (if used): verify point mapping and event reporting.
Confirm DI/DO status, analog values, and alarms upload correctly to DCS/SCADA.
7. On-Site Live Verification (Primary Energized)
Perform only after all static tests pass and following site safety procedures.
Energize primary equipment; verify real-time current, voltage, power, frequency, and temperature.
Confirm alarms, event logs, and thermal model status.
Validate breaker position feedback and remote interlock logic.
Check 4-20 mA analog outputs to DCS under actual operating conditions.
8. Final Backup & Documentation
Save final setpoints, event logs, and COMTRADE files.
Document firmware version, configuration files, and test results in the commissioning report.
Clear historical events and faults prior to handover.
Provide a communication point list for DCS/SCADA integration.

DS200PTBAG1BBA
DS200TDAH1BHD
DS200TCRAG1ACC
DS200DTRAG1AAA
DS200DTBBG1ABB
DS200SDCCG4AFD
DS200TCDAG1BDB
IS220PTURH1B
C60G01HCHF8FH6PM8FP6PU6PWXX
DS200TCQCG1BHF